Example project · examples/hydro
Example SCADA for a hydroelectric plant.
- Design head
- 82 m
- Units
- 2 × Francis 10 MW
- Speed
- 600 rpm
- Voltage
- 6.3 / 66 kV
- Rated flow
- 14.5 m³/s per unit
- Reservoir
- Max. normal level 815 m

Green means running, amber in transition and red tripped. On the single-line, red means closed and green open.
Start the unit, change the setpoint, stop it or trip it. The sequence follows the simulated PLC logic with compressed timings.
- 1. Auxiliaries start
- 2. Inlet valve opening
- 3. Acceleration
- 4. Excitation
- 5. Synchronisation
- 6. On load
- 7. Unloading
- 8. Disconnection
- 9. Closing and braking
Event log
- Press Start to begin.
Siemens S7
PLC_G1
DB1 · 116 bytes · 250 ms
Commands, sequence, governor, protections and measurements of unit 1.
Siemens S7
PLC_G2
DB1 · same map · 250 ms
Same program and addresses as unit 1.
Siemens S7
PLC_SSCC
DB1 · 500 ms
Reservoir, spillway, intake, 66 kV substation and auxiliary services.
Modbus TCP
Contador_66kV
float32 + uint32 · 1 s
Boundary revenue meter: power, voltage, frequency and energy.
| Signal | Alarm | Trip |
|---|---|---|
| Guide bearing | 70 °C | 80 °C |
| Thrust bearing | 75 °C | 85 °C |
| Stator winding | 110 °C | 130 °C |
| Vibration | 4.5 mm/s | 7.1 mm/s |
| Oil pressure | 52 bar | 45 bar |
| Speed | — | 115 % |
| 66 kV grid | — | Loss with unit on line |
- 01Start Unit 1 and follow the sequence to ON LOAD.
- 02Lower the setpoint to 3.5 MW and watch the rough-zone warning.
- 03Heat the thrust bearing: acknowledge the alarm and wait for the trip.
- 04Reset the 86 lockout and start again.
- 05Cause a grid loss with both units on load and recover the plant.
- 06Simulate a flood: the spillway opens by itself to hold the reservoir.
The simulated PLCs ship inside abSCADA: no hardware needed.
- 01Download abSCADA for Windows and open abscada.exe.
- 02On the start screen, pick the example and keep «Also start its simulated PLC» ticked.
- 03Click Open runtime in Studio.
Example scope
It is a teaching example, not a certified system. Timings are compressed (a start takes about 40 s), the reservoir reacts about 200 times faster than reality and the machine model is approximate. A real plant's protections live in relays and PLCs, never in the SCADA.